8.7 Parameter Modbus Addresses

 

This is a complete list of parameters available in the 800 range, some of which are only available through comms. These addresses are also shown in iTools.

 

Parameter Mnemonic

Parameter Name

Modbus Address

Decimal

PVInValue

PV (Temperature) Input Value

123

TargetSP

Target Setpoint.

NB – do not write continuously changing values to this variable. The memory technology used in this product has a limited number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function or the Alternative Setpoint available over comms (Modbus address 26 )in preference.

2

 

OP

Manual Output Value (resolution 0.1%, i.e. 50% output = 500)

130 and 132

WorkingOP

Working Output

4

WorkingSP

Working Setpoint (Read Only)

5

Pb

Proportional Band

6

Ti

Integral Time (0 = No Integral Action)

8

Td

Derivative Time (0 = No Derivative Action)

9

AL1

Alarm 1 Threshold

13

AL2

Alarm 2 Threshold

310

SP.SL

Active Setpoint Select (0 = Setpoint 1; 1 = Setpoint 2)

15

d.bnd

Channel 2 Deadband

16

cb.Lo

Cutback Low

17

cb.Hi

Cutback High

18

r2G

Relative Cool Gain

19

t.st

Timer Status (0 = Reset; 1 = Run; 2 = Hold; 3 = End)

23

SP1

Setpoint 1

NB – do not write continuously changing values to this variable. The memory technology used in this product has a limited number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function or the Alternative Setpoint (Modbus address 26) in preference.

138

SP2

Setpoint 2

25

AltSP

 

 

 

Alternative setpoint (comms only parameter) may be used as a setpoint or to ramp the setpoint providing a value has been received within a window of about 5 seconds. This may be enabled using the AltSPSelect (address 276). If no value is received then the controller falls back to the currently selected setpoint (SP 1 or SP 2). The Alternative Setpoint may have a local trim (SP Trim, address 27) added to it to compensate for variations in temperature in a particular zone.

 

This parameter is not saved when the instrument is switched off. It may be written to continuously over communications without risk of damage to the instrument non-volatile memory.

26

SPTrim

Local Trim – added to the remote setpoint to compensate for local temperature variations in a control zone.

27

Mr

Manual Reset

28

oP.Hi

Output High Limit

30

oP.Lo

Output Low Limit

31

SP.rr

Setpoint Rate Limit Value (0 = no rate limit)

35

Error

Calculated Error (PV-SP)

39

AL1.H

Alarm 1 Hysteresis

47

AL2.H

Alarm 2 Hysteresis

68

AL3.H

Alarm 3 Hysteresis

69

InstStatus

 

Instrument Status. This is a bitmap:

B0 – Alarm 1 Status

B1 – Alarm 2 Status

B2 – Alarm 3 Status

B4 – Auto/Manual Status

B5 – Sensor Break Status

B6 – Loop Break Status

B7 – CT Low load current alarm status

B8 – CT High leakage current alarm status

B9 – Timer End

B10 – PV Over-range (by > 5% of span)

B11 – CT Overcurrent alarm status

B12 – New Alarm Status

B13 – Timer/Ramp Running

B14 – Remote (comms) SP Fail

B15 – Auto-tune Status

In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.

75

 

InverseStatus

Inverted Instrument Status. This is an inverted (bitwise) version of the preceding parameter and is provided so that scrolling messages can be triggered when a condition is not active. Bit mappings are as the “Instrument Status”, Modbus address 75

76

InstStatus2

Instrument Status 2. This is a bitmap similar to InstStatus and provides a summary of the main instrument status indicators.

B0 – EEPROM Write Frequency Warning Flag

No further bits are used in the current firmware.

77

Ld.A

Load ON Current

80

AL3

Alarm 3 Threshold

177

HyS

Ch1 On/Off Hysteresis in Eng Units

86

DigIPStatus

Digital Inputs Status. This is a bitmap:

B0 – Not used

B1 – Logic input LA

B2 – Logic input LB

B7 – Power has failed since last alarm acknowledge

A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not configured as inputs.

87

HyS.C

Ch2 On/Off Hysteresis in Engineering Units

88

FiLt

Input Filter Time (0 = Off)

101

SP.Hi

Setpoint High Limit

111

SP.Lo

Setpoint Low Limit

112

oFS

PV Offset

141

C.Adj

Calibration Adjust

146

IM

Instrument Mode (0 = Operating mode - all algorithms and I/O are active

1 = Standby - control outputs are off

2 = Config Mode - all outputs are inactive)

199

MVInVal

Input value in millivolts (comms only parameter).

202

 

 

 

CJCTemp

CJC Temperature

215

SBrk

Sensor Break Status (0 = Off; 1 = Active)

258

NewAlarm

New Alarm Status (0 = Off; 1 = Active)

260

AlLatchStatus

Alarm Latch

261

LoopBreakAlarm

Loop Break (0 = Off; 1 = Active)

263

A.tUn

Auto-tune Enable (0 = Off; 1 = Enabled)

270

A-M

Mode of the Loop (0 = Auto; 1 = Manual)

273

Ac.AL

Acknowledge all alarms (1 = Acknowledge)

274

AltSPSelect

Alternate Setpoint enable (comms only parameter for the Alternative Setpoint ).

276

AltSPPercent

Alternative setpoint in percent

277

AltSPHi

Alternative input high scalar – sets high range for setpoint input, corresponding to 20mA or 10V depending on the input type.

278

AltSPLo

Alternative input low scalar – sets low range for setpoint input, corresponding to 4mA or 0V depending on the input type.

279

AL1Out

Alarm 1 Status (0 = Off; 1 = Active)

294

AL2Out

Alarm 2 Status (0 = Off; 1 = Active)

295

AL3Out

Alarm 3 Status (0 = Off; 1 = Active)

296

Ld.AL

Low Load Current Threshold

304

LE.AL

High Leakage Current Alarm (0 = Off; 1 = Active)

305

Hc.AL

Over Current Alarm Threshold

306

LoadAlarmOut

Load Alarm Status (0 = Off; 1 = Active)

307

LeakAlarmOut

Leak alarm Status.

308

OverAlarmOut

Over Current alarm Status (0 = Off; 1 = Active)

309

Instantaneouscurrent

Instantaneous current

311

SS.SP

Soft Start Setpoint

322

SS.oP

Soft Start Power Limit

323

t.dUr

Requested Timer Duration

324

t.EL

Elapsed Time

325

t.rE

Time Remaining

326

t.thr

Timer Start threshold

327

Unit

Display Units (0 = Degrees C ; 1 = Degrees F; 3 = None)

516

uCAL

User Calibration Enable (0 = Off; 1 = Lo; 2 = Hi; 3 = Reset)

533

DigOPStatus

 

 

 

 

 

 

 

Digital Outputs Status. This is a bitmap:

B0 – Output 1

B1 – Output 2

B2 – Output 3 on 808 and 804 controllers

B3 – Output 4

It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose function is set to ‘none’ are affected, and the setting of any bits in the Digital Output Status word will not affect outputs used for heat (for example) or other functions. Thus it is not necessary to mask in the settings of these bits when writing to this variable.

551

 

 

 

 

 

 

 

AdjustHighOffset

Adjust High Offset

560

AdjustLowOffset

Adjust Low Offset

561

AdjustHighPoint

Adjust High Point

562

AdjustLowPoint

Adjust Low Point

563

Goto

Select access level

7935

P1

Input Type and Range

9001

P2

Decimal Point Position

9002

P3

Low Scale Range Value

9003

P4

High Scale Range Value

9004

P5

Linear Input Low Millivolts

9005

P6

Linear Input High Millivolts

9006

P7

Control Output and Type

9007

P8

Non Linear Cooling Type

9008

P11

Output 1 Function

9011

P12

Output 2 Function

9012

P13

Output 3 Function

9013

P14

Output 4 Function

9014

P15

DC Out Range

9015

P16

Retransmission Initial Scale Value

9016

P17

Retransmission Full Scale Value

9017

P21

Alarm 1 Type

9021

P22

Alarm 1 Latching

9022

P23

Alarm 1 Blocking

9023

P24

Alarm 2 Type

9024

P25

Alarm 2 Latching

9025

P26

Alarm 2 Blocking

9026

P27

Alarm 3 Type

9027

P28

Alarm 3 Latching

9028

P29

Alarm 3 Blocking

9029

P31

Current Transformer Source

9031

P32

Current Transformer Range

9032

P33

Current Transformer Alarm Latching

9033

P34

Loop Break Alarm Time

9034

P35

Sensor Break Alarm Type

9035

P36

Sensor Break Safe Output Power

9036

P37

Break Alarms Output

9037

P41

Timer Configuration

9041

P42

Timer Resolution

9042

P43

Timer End Type

9043

P44

Operative setpoint at start up

9044

P51

Logic input 1 function

9051

P52

Logic input 2 function

9052

P61

Digital communications address

9061

P62

Digital communications baud rate

9062

P63

Digital communications parity

9063

P64

Communications master retransmission parameter

9064

P65

Communications master retransmission address

9065

P71

F1 pushbutton functionality

9071

P72

F2 pushbutton functionality

9072

P73

Page pushbutton functionality

9073

P74

Home display second line content

9074

P75

Home display third line content

9075

P76

Level 2 passcode

9076

P77

Configuration level passcode

9077

rEc.S

Recovery point save

9101

rEc.L

Recovery point load

9102

PHAS

Calibration phase

9103

Go

Calibration start

9104

vAL

Calibration analogue output value

9105

 

 

 

IPAType

Logic Input 1 channel hardware type (0 = None; 1 = Logic Inputs)

12352

IPBType

Logic Input 2 channel hardware type (808 and 804 only) (0 = None; 1 = Logic Inputs)

12368

CommsType

Digital Communications Module Type (0 = None; 1 = EIA485)

12544

CTType

Current Transformer (0 = None; 1 = CT in)

12608

OP1Type

IO channel 1 hardware type (0 = None; 1 = Relay; 2 = Logic I/O)

12672

1.PLS

IO1 Time proportioning Output minimum pulse time

12706

OP2Type

Output 2 Type (0 = None; 1 = Relay; 2 = Logic; 3 = DC OP [816 only]

12736

2.PLS

Output 2 Time proportioning Output minimum pulse time

12770

OP3Type

Output 3 Type (0 = None; 1 = Relay; 3 = DC OP [808 and 804 only])

12800

3.PLS

Output 3 Time proportioning Output minimum pulse time

12834

OP4Type

Output 4 Type (0 = None; 1 = Relay)

13056

4.PLS

Output 4 Time proportioning Output minimum pulse time

13090